Pendent Fire Sprinkler Head, Quick Response, 3/4 in, 14.0 K, 165 deg F, Bronze
PartRELJL141B
MFGJL141B
Description
Reliable® JL141B Commercial Sprinkler, ESFR Pendent, Series: JL-14, 175 psi, 3/4 in, 14.0 Nominal K-Factor, NPT, 165 deg F, Bronze, Black
Price/Availability Accessible On Login
- Deflector should be parallel with the ceiling or roof
The Reliable® model JL-14 Early Suppression fast response (ESFR) sprinkler is intended for use against severe fire challenges. This sprinkler is designed to respond quickly to growing fires and will deliver a heavy water discharge to "suppress" rather than "control" fires. Note: the model JL-14 ESFR sprinkler utilizes a levered fusible alloy solder link in either a 165 deg F (74 deg C) or a 212 deg F (100 deg C) rating. FM global considers this a "Quick Response" storage sprinkler for use in data Sheet 8-9. The sprinkler has a nominal K factor of 14.0 (metric 200) and will deliver approximately 100 gpm (378 Lpm) of water at 50 psi (3.5 bar). The deflector and frame provide a broad, very symmetrical, hemispherical pattern capable of suppressing fires between sprinklers in high storage height areas and at the same time retaining a high momentum central core to penetrate and suppress fires occurring directly beneath the sprinkler in low storage height areas.
Thread Size | 3/4 in |
Nominal K-Factor | 14.0 K |
Temperature Rating | 165 deg F |
Type | Pendent |
Finish/Color | Bronze |
Color Family | Bronze |
Activation Type | Quick Response |
Color | Bronze |
Connection Type | NPT |
Pressure Rating | 175 psi |
Series | JL-14 |
Brand | Reliable® |
UNSPSC | 46191602 |
Alternate Part Number 1 | D816114298 |
Manufacturer | Reliable Automatic Sprinkler Co |
Manufacturer Part Number | JL141B |
CNBOP-PIB|cULus Listed|FM Approved|LPCB|VdS Approved|PROP65: Cancer and Reproductive Harm - www.P65Warnings.ca.gov